手算估算 · Hand calculation
用浮力壓差與開口流量公式估算量級,作為模擬結果的對照。
Standard stack-pressure and orifice-flow equations give the order of magnitude and a check on the simulation.
Research Note · Experiments
浮力通風靠的是什麼?外部有風時又會怎樣?這份筆記用簡化的瀏覽器流體模擬,檢討「以高度產生溫度差來帶動空氣」的設計構想。
Airflow in space: an early study of stack (buoyancy-driven) ventilation and how outdoor wind changes it, using a simplified in-browser fluid solver.
設計上常希望利用挑高、天井或通風塔,讓熱空氣往上排、涼空氣從下方補進來。這份研究想釐清四件事:
We asked what drives stack ventilation and how strong it is, what happens when outdoor air is hotter than indoor air, how wind changes the flow in a two-storey block with an attached void, and when urban wind modelling becomes necessary.
用浮力壓差與開口流量公式估算量級,作為模擬結果的對照。
Standard stack-pressure and orifice-flow equations give the order of magnitude and a check on the simulation.
自行撰寫、在瀏覽器執行的流體求解器,用來看氣流路徑與冷熱分層,比較不同開口配置。
A custom browser solver shows flow paths and thermal layering, and compares opening layouts.
| 項目 Item | 做法 Approach |
|---|---|
| 基礎方法 Basis | Stable Fluids(Stam, 1999)的不可壓縮流簡化解 · simplified incompressible Navier–Stokes |
| 對流 Advection | 半拉格朗日法,三線性內插 · semi-Lagrangian with trilinear interpolation |
| 壓力 Pressure | SOR 疊代解 Poisson 方程,每步 24~28 次(未完全收斂)· SOR, 24–28 iterations per step, not fully converged |
| 浮力 Buoyancy | Boussinesq 近似 · Boussinesq approximation |
| 溫度 Temperature | 以鬆弛方式拉回設定溫度,代表空調或蓄熱,非熱傳計算 · relaxed toward set points, not a heat-transfer model |
| 外部風 Wind | 邊界固定冪次律剖面,指數 0.2、基準高度 10 m · power-law profile, α = 0.2, reference 10 m |
| 網格 Grid | 案例一 25 cm、案例二 40 cm · 25 cm (case 1), 40 cm (case 2) |
4 × 6 m、高 12 m,室內 30 °C、室外 36 °C,上下各一個 1 × 2 m 開口,開口中心高差約 10.4 m,不考慮外部風。
Case 1: a 4 × 6 × 12 m volume, 30 °C inside and 36 °C outside, one 1 × 2 m opening low and one high, about 10.4 m apart, no wind.
東西 6 m × 南北 8 m、兩層各 4 m;東西兩側每層三扇 1.2 × 1.5 m 窗;東牆中央外接 2 × 3 × 8 m 挑空,上下各一開口。西南風 2.5 m/s(10 m 高),室外 30 °C、室內 31 °C。
Case 2: a 6 × 8 m two-storey block (4 m per floor) with three 1.2 × 1.5 m windows per floor on the east and west, and a 2 × 3 × 8 m void attached to the east wall. South-west wind at 2.5 m/s (10 m height).
空氣被開口兩側空氣柱的壓力差推動。誰比較熱,決定了方向;室內外同溫時,就算室內很熱也不會換氣。
Flow is driven by the indoor–outdoor temperature difference. Which side is warmer sets the direction.
案例一估算約 2.3 Pa、6,100 m³/h、每小時換氣約 21 次,同時帶入約 12 kW 熱量。冷氣從下方流失,熱空氣從上方灌入。
With outdoor air hotter, flow reverses: about 6,100 m³/h and roughly 12 kW of heat gain in case 1 (sample data).
案例二屋頂高度風速約 2.4 m/s,動壓約 3.3 Pa;挑空沒有日照增溫時浮力趨近零。這時由風壓主導。
At 2.4 m/s roof-height wind, dynamic pressure (about 3.3 Pa) far exceeds void buoyancy, so wind dominates.
西立面正壓、全部進風;東立面負壓、全部排風。挑空在背風側,上下開口都往外排,把東側房間的空氣吸進挑空後帶走。
The leeward void acts as an exhaust shaft, drawing air from the east rooms and venting through both openings.
反向煙囪效應
| 開口群組 Opening group | 方向 Direction | 流量 Flow (m³/h) |
|---|---|---|
| 西側 1F 三窗 · West, 1F | 進風 In | ≈ 18,500 |
| 西側 2F 三窗 · West, 2F | 進風 In | ≈ 24,400 |
| 東側 1F 外窗 · East, 1F | 排風 Out | ≈ 10,800 |
| 東側 2F 外窗 · East, 2F | 排風 Out | ≈ 11,900 |
| 1F → 挑空 · 1F to void | 流入挑空 To void | ≈ 4,700 |
| 2F → 挑空 · 2F to void | 流入挑空 To void | ≈ 6,100 |
| 挑空下開口 · Void, low | 排風 Out | ≈ 2,600 |
| 挑空上開口 · Void, high | 排風 Out | ≈ 3,200 |
粗網格與壓力未完全收斂,進風總量與排風總量相差約三成,流量應視為趨勢與相對比較,絕對值很可能高估。· Inflow and outflow totals differ by about 30% because of the coarse grid; read these as relative trends.
No turbulence model, coarse grid, uncalibrated pressure coefficients, incomplete convergence, simplified temperature, open terrain. Suitable for comparing layouts, not for design values or compliance.
Close high openings while cooling, use the stack for night purging, consider a solar chimney for daytime use, and keep exhausts in negative-pressure zones.
在密集市區,鄰棟遮擋與街道導風會改變開口實際受到的風向、風速與立面風壓;市區常見的無風時段反而是浮力通風的主場;熱島效應與鄰棟設備排熱也會提高進風溫度、削弱溫差。實務上通常分尺度串接:街廓尺度取得局部風場與風壓係數,再交給建築尺度的多區氣流網路計算各房間換氣量,必要時才做室內 CFD。
In dense urban sites, neighbouring buildings change local wind and facade pressures, calm periods make buoyancy more important, and urban heat raises intake temperatures. A practical chain is neighbourhood CFD for local wind and pressure coefficients, then a multizone airflow network, then room-scale CFD only where needed.
| 尺度 Scale | 工具舉例 Example tools | 產出 Output |
|---|---|---|
| 街廓 Neighbourhood | OpenFOAM、ENVI-met、PALM-4U | 局部風速風向、立面風壓係數、微氣候溫度 |
| 建築 Building | CONTAM、EnergyPlus AirflowNetwork | 風壓與浮力共同作用下各房間換氣量 |
| 室內 Room | OpenFOAM 等 CFD 軟體 | 細部流場、死角 |
本頁所有案例、數值與圖示皆為假設條件下的示意資料,不代表任何實際建築或專案,不可作為設計值或法規檢討依據。· All cases, values and diagrams are sample data under assumed conditions and do not represent any real building or project.